Outdoor Unit Control
SiME281906E
61
Part 4 Functions and Control
4.12 High Pressure Protection Control
In order to prevent abnormal high pressures in the system and hence avoiding activation of the
high pressure safety device the below control function will be activated.
Flowchart
As the bearing resistance limit pressure decreases during slow operation of the compressor, the
lower limit of frequency is restricted.
In cooling
Parameters
Normal operation
Hp >
B
MPa
Compressor operation
frequency –1 step/10 seconds
Compressor operation
fre1 step/1 minute
Compressor operation
frequency
A
Hz
Compressor operation
fre1 step/5 minutes
Hp >
C
p
H
a
P
M
≤
G
MPa
OR
Hp <
E
MPa
Compressor stop
Abnormal stop (
E3
indication)
15 times or less
stopping in 300 minutes
Hp
≤
F
MPa
• Stopped 16 times in 300 minutes
• High pressure switch is activated.
• Hp >
D
MPa for 1 minute
Hp
≥
2.55 MPa
Normal operation
Hp < 2.36 MPa
After 30 seconds
Compressor
frequency lower limit
H
Hz
RZF18/24AVMK
RZF30/36AVMK
A
(Hz)
88.5
88.5
B
(MPa)
3.67
3.67
C
(MPa)
3.77
3.77
D
(MPa)
4.02
4.02
E
(MPa)
3.62
3.62
F
(MPa)
3.39
3.39
G
(MPa)
3.52
3.52
H
(Hz)
63
64.5
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...