SiME281906E
Field Settings with Remote Controller
Part 5 Field Settings and Test Operation
76
Note(s)
1.5.7 Airflow Adjustment (AUTO)
Make external static pressure setting automatically using automatic airflow adjustment
(11 (21)-7), or manually using external static pressure settings (13 (23)-6).
The volume of blow-off air is automatically adjusted to the rated quantity.
Make settings before performing the test operation of the outdoor unit.
Setting procedure
1. Make sure that electric wiring and duct construction have been completed.
In particular, if the closing damper is installed on the way of the duct, make sure that it is
open. In addition, make sure that a field-supplied air filter is installed within the air
passageway on the suction port side.
2. If there are multiple blow-off and suction ports, adjust the throttle part so that the airflow
volume ratio of each suction/blow-off port conforms to the designed airflow volume ratio. In
that case, operate the unit with the operation mode "fan". When you want to change the
airflow rate, adjust it by pressing the airflow rate control button to select High, Middle or Low.
3. Make settings to adjust the airflow rate automatically.
After setting the operation mode to "fan", enter the field setting mode while operation is
stopped and then select the Mode No. 11 (21), set the First Code No. to
7
and the Second
Code No. to
03
. After setting, return to the basic screen (to the normal mode in the case of a
wireless remote controller) and press the ON/OFF button. Fan operation for automatic
airflow adjustment will start with the operation lamp turned ON. Do not adjust the throttle part
of the suction and blow-off ports during automatic adjustment. After operation for
approximately one to fifteen minutes, airflow adjustment automatically stops with the
operation lamp turned OFF.
4. After operation stopped, make sure that the Second Code No. is set to
02
as in the following
table by indoor unit with the Mode No. 11 (21). If operation does not stop automatically or the
Second Code No. is not set to
02
, return to the step (3) above to make settings again.
: Factory setting
1. Make sure that the external static pressure is within the range of specifications before
making settings. If it is outside the range, automatic adjustment fails, which may cause an
insufficient airflow volume or leakage of water.
2. If the air passageway including duct or blow-off ports is changed after automatic adjustment,
make sure to perform automatic airflow adjustment again.
1.5.8 External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T2 terminal of the operation terminal block in the electrical
component box.
: Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
7
01
OFF
02
Completion of airflow adjustment
03
Start of airflow adjustment
Mode
No.
First Code
No.
Second
Code No.
Contents
12 (22)
1
01
ON: Forced OFF (prohibition of using the remote controller)
OFF: Permission of using the remote controller
02
OFF
ON: Operation
ON
OFF: Stop
F2 T1 T2
Forced OFF
Input A
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...