Troubleshooting by Error Code
SiME281906E
151
Part 6 Service Diagnosis
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
CHECK 8
Turn OFF the power supply once and
then turn ON again.
Connect the connector
properly.
YES
YES
Is the
electronic expansion
valve connector properly
connected to the outdoor
unit main PCB?
(
∗
1)
NO
NO
YES
Replace the electronic
expansion valve coil.
Is the coil
resistance of the electronic
expansion valve normal?
NO
A
Error is displayed again?
Mount the thermistor properly.
Is the
thermistors
(suction pipe,
discharge pipe, heat
exchanger middle, and
outdoor heat exchanger
distributor pipe thermistors)
mounted properly?
NO
YES
Go to the next page