SiME281906E
Check
Part 6 Service Diagnosis
192
6. Check
6.1 Thermistor Check
CHECK 1
If the cause of the problem is related to the thermistors, then the thermistors should be checked
prior to changing the PCB.
Overview of Thermistors
The table below contains an overview of the thermistors:
Indoor
Outdoor
Checking
To check the thermistors, proceed as follows:
Thermistor
FDFM-A
R1T Suction air thermistor
Type B
R2T Indoor heat exchanger liquid pipe thermistor
Type A
R3T Indoor heat exchanger middle thermistor
Type L
Thermistor
RZF18/24AVMK
RZF30/36AVMK
R1T Outdoor air thermistor
Type M
Type E
R2T Discharge pipe thermistor
Type G
Type G
R3T Suction pipe thermistor
Type A
Type A
R4T
Outdoor heat exchanger distributor
pipe thermistor
Type A
—
Outdoor heat exchanger liquid pipe
thermistor
—
Type A
R5T Outdoor heat exchanger middle
thermistor
Type A
Type A
Step
Action
1
Disconnect the thermistor from the PCB
2
Read the temperature and the resistance value.
3
Check if the measured values correspond with the values in the table on the next pages.
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...