Unit Operation
www.DaikinApplied.com 83
IM 1287-4 • REBEL APPLIED ROOFTOP
Figure 138: Commission Unit Menu Structure
Commission Unit
Unit Set-Up
►
Timer Settings
►
SAF Set-Up
►
RF/EF Set-Up
►
Htg/Clg ChgOvr Set-Up
►
Cooling Set-Up
►
Econo Set-Up
►
OA Damper Set-Up
►
Heating Set-Up
►
Dehum Set-Up
►
Humidity Sensor Set-Up
►
Energy Rec Set-Up
►
Relief Damper Set-Up
►
Space Sensor Set-Up
►
Configurable IO
►
Alarm/Event Config
►
Unit Set-Up
Eng Units= English
UnitName= xxxxxxxx
Loc Space T Cfg= Sen1
Emerg Stop= ManClr
Timer Settings
Start Up= 180s
Recirculate= 180s
Clg Stg Time= 5min
Htg Stg Time= 5min
Zero OA Time= 0m
Tnt Ovrd Incr= 120min
Post Heat= 0s
Low DAT= 6min
Service Time= 0min
Htg/Clg ChgOvr Set-Up
Ctrl Temp Src= RAT
RemSptSrc= None
Control Temp= XXX°F
Occ Clg Spt= 72.0°F
Occ Htg Spt= 68.0°F
Occ Clg DB= 2.0°F
Occ Hlg DB= 2.0°F
CalRemSpt@10°C=No
CalRemSpt@50°F=No
CalRemSpt@30°C=No
CalRemSpt@86°F=No
DemandShed=Enable
Cooling Set-Up
Circ1 CmpState=________
Circ2 CmpState=________
FCmp1=_______________
FCmp2=_______________
FCmp3=_______________
FCmp4=_______________
FCmp5=_______________
FCmp6=_______________
Control Temp= XXX°F
Occ Clg Spt= 72.0°F
Occ Htg Spt= 68.0°F
Disch Air= XXX.X°F
DAT Clg Spt= 72.0°F
DAT Clg DB= 2.0°F
EffSpactT= XXX°F
Unocc Clg Spt= 85.0°F
Unocc Dif f= 3.0°F
Clg Stage Time= 5min
OA Temp= XXX.X°F
Clg Lo OAT Lck= 25°F
OAT Diff= 2°F
Min Clg Spt= 55.0°F
Min Clg Spt @= 0
Clg Reset= None
Max Clg Spt= 65.0°F
Max Clg Spt @= 100
DXBP LCTSpt = 52.0°F
DXBP LCTDB = 2.0°F
DXBPLCTSptReset =None
DXBPMinLCTSpt = 45.0°F
DXBPMinLCTSpt@ = 0
DXBPMaxLCTSpt = 52.0°F
DXBPMaxLCTSpt@ = 100
OA Damper Set-Up
Vent Limit= 20%
LoFlo V Lmt= 30%
DCV Limit= 10%
OAD Position= XXX%
Min OA Pos= XXX%
Min OA Src= ___________
Min OA Reset= None
External Reset
OA @ MinV/mA= 0%
OA @ MaxV/mA= 100%
Min V/mA= 0.0V
Max V/mA=10.0V
CO2 Reset
CO2 Reset= Yes
PPM@DCVLmt= 800PPM
PPM@VntLmt= 1000PPM
CO2 PPM = XXXXppm
CO2 QMXSnsr =QMX1
Flow Reset
OA Flow Reset= Yes
OA Flow= XXXXXCFM
OA Flow Spt= 2000CFM
OA Flow DB= 3%
BSP Reset
BSP OA Ovrd= No
BldgSP Spt= 0.05in
BSP DB= 0.010in
Econo Set-Up
Control Temp= XXX°F
Occ Clg Spt= 72.0°F
Occ Clg DB= 2.0°F
Disch Air= XXX.X°F
UseDATClgSpt=Yes
DAT Econ Spt= 55.0°F
DAT Econ DB= 2.0°F
Clg Stage Time= 5min
Econ Chgovr= EnthOAT
OA Temp= XXX°F
Chgover Temp= 70.0°F
Econo Dif f= 2°F
Econo FDD= On
Econo Reset= None
Min Econ Spt= 55.0°F
Min Econ Spt @= 0
Max Econ Spt= 65.0°F
Max Econ Spt @= 100
Max OAT Lmt @= 75°F
Min OAT Lmt @= 70°F
Calibrate OAD=No
Pos Sw Open= 97%
Max Sw Diff= 3%
Pos Sw Close= 3%
Min Sw Diff= 5%
OAD Sw Status=_________
OAEOffset= 0.0°F
OADewpoint=___________
OARelHum=____________
OAEnthalpy=___________
RADewpoint=___________
RARelHum=____________
RAEnthalpy=____________
DATSptEnth=___________
Heating Set-Up
Control Temp= XXX°F
Occ Htg Spt= 68.0°F
Occ Hlg DB= 2.0°F
Disch Air= XXX.X°F
DAT Htg Spt= 85.0°F
DAT Htg DB= 2.0°F
EffSpactT= XXX°F
Unocc Clg Spt= 85.0°F
Unocc Dif f= 3.0°F
Htg Stage Time= 5min
OA Temp= XXX.X°F
Htg Hi OAT Lk= 55°F
OAT Diff= 2°F
Htg Reset= None
Min Htg Spt= 55.0°F
Min Htg Spt @= 0
Max Htg Spt= 120.0°F
Max Htg Spt @= 100
Min DAT Ctrl= Yes
Min DAT Limit= 55.0°F
MWU Sensor= CtrlTemp
StgGpriState= ____
StgGSpltState= ____
StgGDiagCode= ____
ModGState= ____
ModGDiagCode= ____
ModGErrCode= ____
F&BP Method= OpenVlv
F&BP ChgOvrT= 37°F
Humidity Sensor Set-Up
Hum Sensor 1= SpaceH1
Hum Sensor 2 = OAH
SpcHumSensType = VDC
SpcHum MinSig= 0.0V
SpcHum MaxSig= 10.0V
SpaceRel Hum 1= __________
SpaceDwpnt1= ____________
SpaceRel Hum2= __________
SpaceDwpnt2= ____________
RARelHum= ______________
RADewpoint= _____________
OARelHum= ______________
OADewpoint= _____________
Relief Damper Set-Up
Exh Plen Press=X.XXXin
Ef fExh PSP Spt= _____
Rel Dmpr Cmd= _____
ExhPSP Lo Spt= 0.150in
ExhPSP Hi Spt= 0.350in
Exh PSP DB= 0.050in
Configurable I/O
Apply IO Chgs= No
X1 Cfg= AI_V
Input X1=_______________
X2 Cfg= AI_V
Input X2= ______________
X3 Cfg= AI_V
Input X3=_______________
X4 Cfg= AI_V
Input X4= ______________
X5 Cfg= AI_V
Input X5=_______________
X6 Cfg= AI_V
Input X6= ______________
X7 Cfg= AI_V
Input X7=_______________
X8 Cfg= AI_V
Input X8= ______________
Dehum Set-Up
Dehum Method= None
RelHum 1=XXX%
RelHum 2=XXX%
Hum 1 Spt=50%
Hum 2 Spt=50%
Dewpoint 1=XXX°F
Dewpoint 2=XXX°F
Dewpnt 1 Spt=XXX°F
Dewpnt 2 Spt=XXX°F
Rel Hum DB = 2%
Dewpoint DB= 2°F
LCT Setpoint= XXX°F
LCT Spt Reset= None
Min LCT Spt= 45°F
Min LCT Spt@= 0.0
Max LCT Spt= 52.0°F
Max LCT Spt@= 100
Min Rheat Spt= 55.0°F
Max Rheat Spt= 65.0°F
DAT Clg DB= 2.0°F
DAT Htg DB= 2.0°F
Unocc Dehum= No
Energy Rec Set-Up
Energy Rcvy= Yes
ER Wheel= ____________
Wheel Cap= XXX%
Whl Spd Cmd= XXX%
ERWhlRotSw= __________
ER1ErrStatus= __________
ER2ErrStatus= __________
ER LWT= XXX°F
ER EWT= XXX°F
RARelHum=XXX%
Space Sensor Set-Up
CommissionSnsrs= No
Sensor1SN= 000000
Sensor2SN= 000000
Sensor3SN= 000000
SerialNo1= _____________
SerialNo2= _____________
SerialNo3= _____________
Alarm/Event Config
Alarm Limits
Hi Disch Temp= 170°F
Lo Disch Temp= 40°F
Hi Return Temp= 120°F
Alarm Out Config
Faults= Fast
Problems= Slow
Warnings= Off
SAF Set-Up
SAF Ctrl= CAV
Speed Control
Rem SAF Cap= 33%
DSP Control
SAF DuctPress= X.Xin
SAF DSP Spt= 1.0in
SAF DSP DB= 0.1in
1 Zone VAV Control
Control Temp= XXX°F
Occ Clg Spt= 72.0°F
Occ Htg Spt= 68.0°F
Occ Clg DB= 2.0°F
Occ Hlg DB= 2.0°F
CO2 Control
Min SAF PPM= 800ppm
Max SAF PPM= 1100ppm
Min PPM Cap= 50%
Max PPM Cap= 100%
Flow Control
OA Flow= XXXXXCFM
OA Flow Spt= 20
OA Flow DB= 3%
SAF Flow= XXXXXCFM
SAF Flow Spt= 2000CFM
SAF Flow DB= 3%
BSP Control
Bldg Press= X.XXin
BldgSP Spt= 0.05in
BSP DB= 0.010in
SAF Setup
Max SAF Hz= 60Hz
Max SAF RPM= 2600RPM
Min Clg Spd= 40%
Max Clg Spd= 100%
Min Htg Spd= 40%
Max Htg Spd= 100%
VAVBox Out=___________
SAF Status=____________
SAF1 Status=___________
SAF2 Status=___________
SAF3 Status=___________
SAF4 Status=___________
RF/EF Set-Up
RF/EF Ctrl= BSP
Speed Control
RFEF Cap= 5%
BSP Control
Bldg Press= X.XXin
BldgSP Spt= 0.05in
BSP DB= 0.010in
Fan Tracking Control
Sup Fan Max= 100%
RFEF @ SF Max= 95%
Sup Fan Min= 30%
RFEF @ SF Min= 25%
RAF DSP Control
RAF DuctPress= X.X
RAF DSP Spt= -1.0 in
RAF DSP DB= 0.10in
Flow Control
RFEF Flow= XXXXXCFM
RFEF Flow SPT= 2000CFM
RFEF Flow DB= 3%
Flow Diff Control
SAF Flow= XXXXXCFM
RFEF Flow= XXXXXCFM
Min Flow Diff= 0CFM
Max Flow Diff= 0CFM
SAF Lo Flow= 150CFM
SAF Hi Flow= 748CFM
Flow Diff Spt= XXXXCFM
Flow Diff DB= 15 CFM
OAD Position Control
ExhOnOAPos= 40%
ExhMxOAPos= 100%
RFEF Setup
Max RFEF Hz= 60Hz
Max RFEF RPM= 2600RPM
Min RFEF Cap= 5%
Max RFEF Cap= 100%
RFEF Status=______________
RFEF1 Status=_____________
RFEF2 Status=_____________
RFEF3 Status=_____________
RFEF4 Status=_____________
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......