Unit Wiring
www.DaikinApplied.com 53
IM 1287-4 • REBEL APPLIED ROOFTOP
Table 9: Non-Fused Disconnect Lug Port Details
Non Fused
Type 1 Ports
Type 2 Ports
Disconnect
Size
Qty
Min
AWG
Max
AWG
Qty
Min Awg
Max Awg
30
1
#10
2/0
—
—
—
60
1
#10
2/0
—
—
—
100
1
#10
2/0
—
—
—
200
1
#6
300MCM
—
—
—
400
2
1/0
250MCM
1
#4
600MCM
Table 10: Fused Disconnect Lug Port Details
Fused
Type 1 Ports
Type 2 Ports
Disconnect
Size
Qty
Min
AWG
Max
AWG
Qty
Min Awg
Max Awg
60
1
#14
#6
—
—
—
100
1
#12
#1
—
—
—
200
1
#6
300MCM
—
—
—
400
2
1/0
250MCM
1
#4
600MCM
Table 11:
Power Block Port Details
Power
Block
Type 1 Ports
Type 2 Ports
Ampacity
Qty
Min
AWG
Max
AWG
Qty
Min Awg
Max Awg
510
1
#2
600MCM
12
#14
#4
760
4
#4
500MCM
—
—
—
950
2
1/0
750MCM
10
#14
2/0
Copper wire is required for all field installed conductors.
Supply voltage must not vary by more than 10% of the unit
voltage specified on the nameplate. Phase voltage imbalance
must not /- 2%. (Calculate the average voltage of
the three legs. The leg with voltage deviating the farthest from
the average value must not be more than 2% away.) Contact
the local power company for correction of improper voltage or
phase imbalance.
The unit has an option to come with a GFCI service outlet
pre-installed in order to satisfy the code requirements of NEC
210.63. If the GFCI or the service lights were selected as field
powered, conductors supplying a 115V 20/15A source must be
run to terminals in the control panel as shown in the example
in
. These terminals are typically located in the Main
Control Panel at the High Voltage Terminal Block, TBHV.
If the GFCI or service lights were selected as unit powered,
then no additional wiring must be run beyond the 3 phase
service conductors to power the 115V service outlet. Consult
the Unit Specific Electrical Schematics to determine the
installation requirements.
Figure 107: Typical Field Power Entrance – Main Control Box
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......