Installation
www.DaikinApplied.com 29
IM 1287-4 • REBEL APPLIED ROOFTOP
properly installed and fully closed to prevent the entry
of animals and debris through the supply and return air
openings.
7. Cover the supply and return air openings on units without
isolation dampers.
shows an example of the rigging instruction label
shipped with each unit.
Figure 39: Rigging and Handling Instruction Label
Lifting Points
Lifting points are predetermined from factory. When lifting,
make sure all factory installed lifting lugs are used. Figure
19 gives examples of typical 4 point and 6 point lifting
configurations. Unit must remain level during all lifts. Also
shown in
, lifting cable angle from vertical should
never be greater than 30°. Be aware that the center of gravity
for each may not necessarily be in the geometric center of the
unit. Refer to certified drawings for center of gravity location.
NOTE:
Be careful of lifting cable proximity to handles to
prevent damage
Figure 40: DPSA Lifting Points
4 Lifting Points
6 Lifting Points
6 Lifting Points (alternative)
30°
MAX
Spreader Bar
30°
MAX
30°
MAX
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......