Installation
www.DaikinApplied.com 37
IM 1287-4 • REBEL APPLIED ROOFTOP
Hot Water or Hot Water Integral Face
and Bypass
CAUTION
Coil freeze possible when the ambient temperature is below 35°F and can
result in poor equipment operation or damage to the equipment. Follow
instructions for mixing antifreeze solution used. Some products have higher
freezing points in their natural state than when mixed with water. The
freezing of coils is not the responsibility of Daikin.
Hot water coils are not normally recommended for use with
entering air temperatures below 35°F (1.6°C). No control
system can guarantee a 100% safeguard against coil freeze-
up. Glycol solutions or brines are the only freeze-safe media
for operation of water coils at low entering air temperature
conditions.
NOTE:
All coils have vents and drains factory installed.
Hot water coils are provided without valves as a standard
unit, requiring field installation of valves and piping. As an
option, the hot water coil is supplied with either a two-way or
three-way valve and actuator motor from the factory. Refer to
the submittal drawings to determine unit configuration. The
submittal drawing will also have information about the line size
connections.
NOTE:
Factory-installed water valves and piping are bronze,
brass, and copper. Dissimilar metals within the
plumbing system can cause galvanic corrosion. To
avoid corrosion, provide proper dielectric fittings as
well as appropriate water treatment when making
a connection to a pipe that is not copper, bronze or
brass.
A factory provided floor knockout location is provided on
every unit equipped with a hot water coil. Refer to the certified
drawings for the recommended piping entrance locations. Seal
all piping penetrations to prevent air and water leakage.
Table 6: Hot Water Connection Size
Hot Water Connections
B
Cabinet
1 Row
1-1/2"
2 Row
2-1/2”
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......