The electric heater should be activated as the first source
of heat and modulate to maintain the heating discharge air
temperature setpoint (for heating) or the cooling discharge
air temperature setpoint setpoint (for minimum discharge air
temperatures). If the electric heater reaches 100% capacity
and cannot meet the discharge air setpoint, the electric heaster
is shut off and the gas furnace is brought on at minimum fire.
The electric heater continues to run at 100% until the furnace
command has been given for 60 seconds. If the gas furnace
reaches minimum fire for a heating stage timer and over shoots
the heating discharge air temperature setpoint, the gas furnace
is shut off and the electric heater is activated and modulated to
maintain the discharge air temperature setpoint.
Figure 169: Electric 1125 MBH, 100:1
The electric heater should be activated as the first source
of heat and modulate to maintain the heating discharge air
temperature setpoint (for heating) or the cooling discharge
air temperature setpoint setpoint (for minimum discharge air
temperatures). If the electric heater reaches 100% capacity
and cannot meet the discharge air setpoint, the electric heaster
is shut off and the gas furnace is brought on at minimum fire.
The electric heater continues to run at 100% until the furnace
command has been given for 60 seconds. If the gas furnace
reaches minimum fire for a heating stage timer and over shoots
the heating discharge air temperature setpoint, the gas furnace
is shut off and the electric heater is activated and modulated to
maintain the discharge air temperature setpoint.
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......