IM 1287-4 • REBEL APPLIED ROOFTOP 114 www.DaikinApplied.com
Unit Maintenance
Figure 164: MQ616SP 800 MBH, 20:1
Daikin MQ616SP furnaces are split into three manifold
sections, partioned as shown in
. Two furnace
control boards are supplied with these furnace models. The
VB1285 control board controls the modulating Section A as
well as the staged section B of the furnace manifold. The
VB1287 control board controls the staged section C. Both the
VB1285 board and the VB1287 require a distinct 0-10VDC
signal as well as a distinct permissive dry contact. These
connections can be made in Terminal Block 2 (TB-2) .Furnace
controls must be operated in tandem to produce the full turn
down.
Figure 165: MQ624SP 1125 MBH, 10:1, 20:1
Daikin MQ624SP furnaces are split into four manifold sections,
partioned as shown in
. Two furnace control boards
are supplied with this furnace model. The VB1285 control
board controls the modulating Section A as well as the staged
section B of the furnace manifold. The VB1287 control board
controls the staged sections C and D. Both the VB1285 board
and the VB1287 require a distinct 0-10VDC signal as well as
a distinct permissive dry contact. These connections can be
made in Terminal Block 2 (TB-2) .Furnace controls must be
operated in tandem to produce the full turn down.
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......