Unit Maintenance
www.DaikinApplied.com 101
IM 1287-4 • REBEL APPLIED ROOFTOP
Table 15: Main Electric Heat Switch Identification
Size Voltage
KW
Amps
High
Temperature
Limit Primary
Switch (Qty .)
High
Temperature
Limit Backup
Switch (Qty .)
1
208
10 – 15
28 – 42
2
1
240
10 – 15
24 – 36
2
1
480
10 – 15
12 – 18
2
1
600
10 – 15
10 – 15
2
1
2
240
20 – 139
48 – 335
2
1
480
20 – 140
24 – 168
2
1
600
25 – 125
24 – 120
2
1
3
240
159
383
2
2
480
159 – 239 192 – 288
2
2
600
149 – 249 144 – 240
2
2
Figure 151: Backup Manual Switch Location
NOTE:
It is not recommended to use the auxiliary electric
heat as a reheat source for space control.
Table 16: ERW Electric Heat Switch Identification
Voltage
KW
Amps
High
Temperature
Limit Primary
Switch (Qty .)
High
Temperature
Limit Backup
Switch (Qty .)
208
10 – 45
28 – 124
3
2
240
10 – 55
25 – 138
3
2
480
10 – 60
13 – 75
3
2
600
10 – 60
10 – 61
3
2
Figure 152: Backup Manual Switch Location
Heat Coil Area
ML1
ML2
ERW Pre Heater
Note: Manual Limits accessible through mist eliminators
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......