Unit Operation
www.DaikinApplied.com 75
IM 1287-4 • REBEL APPLIED ROOFTOP
Emergency Shutdown
The terminals 205 & 206 on TB2 can be used for any field
supplied component that requires a unit emergency shutdown.
When these terminals are used, the factory installed jumper
must be removed.
Freeze Protection
An optional freezestat is available on units with MicroTech 4
control that have hot water, chilled water, or steam heating
coils. The sensing element is located on the downstream
side of the heating coil in the heating section of the unit. If
the freezestat detects a freezing condition and closes, the
MicroTech 4 controller takes different actions, depending on
whether the fans are ON or OFF. The freezestat is an auto
reset type of control; however, the controller alarm that it
causes is manually reset if the fan is on and auto reset if the
fan is OFF.