Unit Maintenance
www.DaikinApplied.com 137
IM 1287-4 • REBEL APPLIED ROOFTOP
Table 38: Furnace Gas Pressure Itemization
Fuel
Modulation
Heat Input Capacity
MBH (kW)
P1 (in .w .c .)
P2 (in . w .c .)
P3
P4
P5
High
Low
High
Low
High
High
Natural Gas
2-Stage
200 (58.6)
400 (117.2
7 (1.7)
3.5 (0.87)
1.06 (0.26)
2-Stage
600 (175.8)
7 (1.7)
3.5 (0.87)
3.5 (0.87)
4-Stage
600 (175.8)
7 (1.7)
3.5 (0.87)
1.06 (0.26)
3.5 (0.87)
1.06 (0.26)
5:1 Modulation
200 (58.6)
7 (1.7)
3.5 (0.87)
0.19 (0.05)
400 (117.2)
7 (1.7)
3.5 (0.87)
0.18 (0.04)
600 (175.8)
7 (1.7)
3.5 (0.87)
0.56 (0.14)
3.5 (0.87)
10:1 Modulation
400 (117.2)
7 (1.7)
3.5 (0.87)
0.16 (0.04)
3.5 (0.87)
600 (175.8)
7 (1.7)
3.5 (0.87)
0.15 (0.04)
3.5 (0.87)
800 (234.5)
7 (1.7)
3.85 (0.96)
0.24 (0.06)
3,2 (0.8)
1125 (329.7)
7 (1.7)
7 (1.7))
0.56 (0.14)
3.5 (0.87)
3.2 (0.8)
3.2 (0.8)
20:1 Modulation
800 (234.5)
7 (1.7)
3.85 (0.96)
0.21 (0.05)
3.85 (0.96)
3.2 (0.8)
1125 (329.7)
7 (1.7)
3.5 (0.87)
0.56 (0.14)
3.5 (0.87)
3.2 (0.8)
3.2 (0.8)
Propane
2-Stage
200 (58.6)
400 (117.2)
11 (2.74)
10.15 (2.53)
3.07 (0.76)
600 (175.8)
11 (2.74)
10.15 (2.53)
10.15 (2.53)
4-Stage
600 (175.8)
11 (2.74)
10.15 (2.52)
3.07 (0.76)
10.15 (2.53)
3.07 (0.76)
5:1 Modulation
200 (58.6)
11 (2.74)
10.15 (2.52)
0.56 (0.14)
400 (117.2)
11 (2.74)
10.15 (2.53)
0.43 (0.11)
600 (175.8)
11 (2.74)
10.15 (2.53)
1.62 (0.40)
10.15 (2.53)
10:1 Modulation
400 (117.2)
11 (2.74)
10.15 (2.52)
0.43 (0.11)
600 (175.8)
11 (2.74)
10.15 (2.52)
1.62 (0.40)
10.15 (2.53)
6:1 Modulation
800 (234.5)
12 (3.0)
11.2 (2.79)
1.24 (0.31)
8.75 (2.18)
1125 (329.7)
11 (2.74)
10.15 (2.53)
4.51 (1.12)
10.15 (2.53)
8.75 (2.18)
8.75 (2.18)
12:1 Modulation
800 (234.5)
12 (3.0)
11.2 (2.79)
1.24 (0.31)
11.2 (2.79)
8.75 (2.18)
1125 (329.7)
11 (2.74)
10.15 (2.53)
1.13 (0.28)
10.15 (2.53)
8.75 (2.18)
8.75 (2.18)
Figure 175: Staged Gas Safety Control
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......