IM 1287-4 • REBEL APPLIED ROOFTOP 134 www.DaikinApplied.com
Unit Maintenance
Before Start-Up
1. Notify inspectors or representatives who may be required
to be present during start-up of gas fuel equipment.
These could include the gas utility company, city gas
inspectors, heating inspectors, etc.
2. Review the equipment and service literature and become
familiar with the location and purpose of the furnace
controls. Determine where the gas and power can be
turned OFF at the unit and before the unit.
3. Determine that power is connected to the unit and
available.
4. Determine that the gas piping, meter, and service
regulator have been installed, tested, and meet the
equipment requirements .
5. Ensure that all required equipment and instruments are
available for startup.
Preliminary Start-Up
1. Close gas main.
2. Check the combustion inducer fan wheel for binding,
rubbing, or loose setscrews.
3.
Confirm supply voltage.
4. Purge the gas lines.
5. Leak check. Using a rich soap-water mixture and a
brush, check the gas lines for leaks. Correct all leaks
before starting furnace.
Operating Procedures
Burner and Gas Manifold Pressure Adjustment
WARNING
FIRE OR EXPLOSION HAZARD
LOCKOUT/TAGOUT all power sources prior to installing the gas furnace.
Failure to follow warnings exactly could result in serious injury, death,
or property damage. Be sure to read and understand the installation,
operation, and service instructions within this manual. Improper installation,
adjustments, alterations, service, or maintenance can cause serious injury,
death or property damage.
—
Do not store or use gasoline or other flammable vapors
or liquids in the vicinity of this appliance.
—
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any product that is fueled by or
contains an open flame.
• Do not touch any electrical switch.
• Do not use any telephone in the building.
• Leave the building immediately.
• Immediately call the gas supplier from a remote
telephone and follow the gas supplier’s instructions.
•
If you cannot reach the gas supplier, call the local fire
department or 911.
—
Installation and service must be performed by a
qualified installer, service agency, or gas supplier.
WARNING
RISQUE D’INCEDIE OU D`EXPLOSION
Le non respect des mises en garde pourrait entrainer des blessures graves,
la mort ou des pertes materielles. Prendre soin de lire et de comprendre les
instructions d’installation, de fonctionement et d’entretien contenues dans
ce guide. Une installatoin, un reglage, une modification, une reparation ou
un entretien inapproprie peut entrainer des blessures graves, la mort ou
des pertes materielles.
—
Ne pas entreposer ni utiliser d’essence ou autre
vapeurs ou liquides inflammables a proximite de cet
appareil ou de tout autre appareil.
—
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ
•
Ne tentez pas d’alumer un appareil.
•
Ne touchez pas a un interupteur; n’utilisez pas de
telephone dan l’edifice ou vous trouvez.
•
Sortez de l’edifice immediatement.
• Appelez immediatement le fournisseurde gas a partir
d’un telephone a l’exterieur de l’edifice. Suivez les
instructions du fournisseur de gaz.
• Si vous ne pouvez joindre le fournisseur de gaz,
appelez les pompiers.
—
L’installation et les reparations doivent etre confiees a
un installatei=ur qualifie ou au fournisseur de gaz.
WARNING
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......