IM 1287-4 • REBEL APPLIED ROOFTOP 102 www.DaikinApplied.com
Unit Maintenance
Installation
The DPSA main electric heater and ERW pre-heater are
factory installed and wired. Field supplied power wiring to be in
accordance with N.E.C. and any existing local codes by trained
qualified installation and service personnel.
Startup
Manual Mode
1. Turn main power ON to the cabinet and electric preheat.
2. Set the process supply fan to deliver at least the
minimum required air flow via MicroTech 4. See cabinet
electric heat data plate for flow rate.
3. Enable electric heater control via MicroTech 4.
4. Input temperature control value via MicroTech 4 and
observe discharge air temperature is responding as
expected.
Automatic Mode:
1. Turn power ON to the cabinet and electric preheat.
2. Set MicroTech 4 to desired control parameters.
Operation
To operate electric heater, make sure all associated control
equipment is on, energize main supply disconnect, and set
controlling thermostat above ambient temperature. This heater
is equipped with automatic and manual reset temperature
limiting controls. If it fails to operate, make sure manual resets
are operative by pushing reset buttons as discussed above.
Maintenance
Check all electrical connections, including field and factory-
made connections, for tightness at least once per year or
operating season. Any filters in the airstream must be kept
clean so that adequate airflow is maintained.
Содержание Rebel Applied DPSA
Страница 15: ...Introduction www DaikinApplied com 15 IM 1287 4 REBEL APPLIED ROOFTOP Figure 17 VFD Inverter Box Components ...
Страница 109: ...Unit Maintenance www DaikinApplied com 109 IM 1287 4 REBEL APPLIED ROOFTOP Figure 159 10kW 50kW Full SCR Control ...
Страница 144: ...IM 1287 4 REBEL APPLIED ROOFTOP 144 www DaikinApplied com Furnace Wiring Diagrams Figure 178 600 MBH 2 Stage ...
Страница 145: ...Furnace Wiring Diagrams www DaikinApplied com 145 IM 1287 4 REBEL APPLIED ROOFTOP Figure 179 600 MBH 4 Stage ...
Страница 147: ...Figure 181 600 MBH 5 1 Modulation 400 MBH and 600 MBH 10 1 Modulation ...
Страница 160: ......
Страница 161: ......