SiBE12-713
Main Functions
Function and Control
61
Inverter Features
The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor air
temperature and cooling / heating load.
Quick heating and quick cooling
The compressor rotational speed is increased when starting the heating (or cooling). This
enables a quick set temperature.
Even during extreme cold weather, the high capacity is achieved. It is maintained even when
the outdoor air temperature is 2°C.
Comfortable air conditioning
A detailed adjustment is integrated to ensure a fixed room temperature. It is possible to air
condition with a small room temperature variation.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency Limits
The following table shows the functions that define the minimum and maximum frequency:
Forced Cooling /
Heating Operation
For more information, refer to “Forced operation mode” on page 97.
60
120
300
45˚C
Air discharge
temperature
inverter
normal heat pump
Start
seconds
(R1187)
Frequency limits
Limited during the activation of following functions
Low
Four way valve operation compensation. Refer to page 86.
High
Input current control. Refer to page 88.
Compressor protection function. Refer to page 86.
Heating Peak-cut control. Refer to page 89.
Freeze-up protection. Refer to page 89.
Defrost control. Refer to page 91.
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...