Troubleshooting
SiBE12-713
258
Service Diagnosis
5.18
Compressor Sensor System Abnormality
Remote
Controller
Display
H0
Outdoor Unit LED
Display
A
5
1
4
2
4
3
1
4
1
Method of
Malfunction
Detection
Fault condition is identified by the supply voltage and the DC voltage which is detected
before the compressor startup.
Fault condition is identified by compressor current which is detected right after the
compressor startup.
Malfunction
Decision
Conditions
The detected valve of the supply voltage and the DC voltage is obviously low or high.
The compressor current doesn't run when the compressor is started.
Supposed
Causes
Reactor disconnection
Compressor disconnection
Outdoor unit PCB defective
Compressor defective