Outdoor Unit
SiBE12-713
318
Removal Procedure
5
Remove the 2 sheets of
putty.
Warning
Ventilate when refrigerant
leaks during the work.
(If refrigerant contacts fire, it
will cause to arise toxic gas.)
6
There is one nut fixing
the compressor.
Remove the nut with an
open-end spanner.
Before working, make
sure that the refrigerant is
empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
7
Heat up the brazed part
of the discharge side
and disconnect (part
"a").
8
Heat up the brazed part
of the suction side and
disconnect (part "b").
9
Lift the compressor up
to remove.
Step
Procedure
Points