SiBE12-713
Control Specification
Function and Control
101
3.15.3
Cooling / Heating Mode Lock
Use the S15 connector to set the unit to only cool or heat.
Setting to only heat (H): Short-circuit pins 1 and 3 of the connector <S15>.
Setting to only cool (C): short-circuit pins 3 and 5 of the connector <S15>.
The following specifications apply to the connector housing and pins.
JST products Housing: VHR-5N
Pin: SVH-21T-1, 1
Note that forced operation is also possible in COOL / HEAT mode.
3.15.4
ECONO-mode-proof Setting
Outline
When installing in hotels, you can make ECONO mode ineffective on the outdoor unit.
Operation
The ECONO mode can be switched over between "effective" and "ineffective" by pressing the
forced operation switch (SW1) and wiring error check switch (SW3) at the same time and
holding them for 5 seconds while the compressor is stopped. The LEDs are lit in turn for 15
seconds to show the ECONO mode status.
The factory setting is "effective".
COOL mode (C)
HEAT mode (H)
5<C>3<H>1
(R1397)
effective
→
ineffective
ineffective
→
effective
LED flashing order
4
→
3
→
2
→
1
1
→
2
→
3
→
4
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...