SiBE12-713
Others
Others
321
1.2
Jumper Settings
1.2.1 When Two Units are Installed in One Room
When two indoor units are installed in one room, the two wireless remote controllers can be set
for different addresses.
How to set the different addresses
Control PCB of the indoor unit
(1) Remove the electrical box.
(2) Cut the address jumper
JA
on the control PCB.
Wireless remote controller
(1) Slide the front cover and take it off.
(2) Cut the address jumper
J4
.
1.2.2
Jumper Setting
(R4417)
ADDRESS
JA
ADDRESS
JA
EXIST
1
CUT
2
ADDRESS
J4
EXIST
CUT
1
2
J4
(R4418)
Jumper
(On indoor PCB)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto start
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB
Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
Fan speed setting ;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...