SiBE12-713
Control Specification
Function and Control
91
3.10
Defrost Control
Outline
Heat Pump Only
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its fixed value when finishing.
Detail
Conditions for Starting Defrost
Under the conditions that the system is in heating operation, 6 minutes after the compressor is
started and more than 38 minutes of accumulated time pass since the start of the operation or
ending the defrosting.
When the outdoor air temperature and the outdoor heat exchanger temperature meet the
following condition for 60 seconds, the defrost control starts.
A< –(19/256)×B+(45/64)×C
A: outdoor heat exchanger temperature
B: output frequency
C: outdoor air temperature
Conditions for Canceling Defrost
The target heat exchanger temperature as the canceling condition is selected in the range of
4°C
≤
Te
≤
12°C according to the air temperature as the following formula.
The target heat exchanger temperature = –(45/64)×(ambient tempe14
The defrost operation surely operates in 120 seconds after the start. (A
→
B)
After then the defrost operation stops at the following conditions.
1. When the heat exchanger temperature reaches the target heat exchanger temperature.
(B
→
C)
2. When 650 seconds have passed after the start even if the heat exchanger temperature does
not reaches the target heat exchanger temperature. (C)
A
B
C
(R6959)
45 54
45 82
PI control
Pulse
Pulse
Pulse
Pulse
Pulse
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...