SiBE12-713
Control Specification
Function and Control
89
3.6
Freeze-up Protection Control
Outline
During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger.
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start and after 30 sec from changing number of operation room.
Control in Each Zone
The zone is determined by the commands from indoor units.
In drooping zone, the frequency decreases 2Hz/20 seconds.
3.7
Heating Peak-cut Control
Outline
Heat Pump Only
During heating operation, the signals being sent form the indoor unit allow the operating
frequency limitation and prevent abnormal high pressure. (The signal from the indoor unit must
be divided as follows.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 min from
operation start and after A sec from changing number of operation room.
Control in Each Zone
The maximum value of heat exchange intermediate temperature of each indoor unit controls the
following (excluding stopped rooms).
In drooping zone, the frequency decreases 6Hz/40 seconds.
In up zone, the frequency increases 2Hz/60 seconds.
(R4561)
Return from stop
Reset zone
Heat exchanger
thermistor temperature
Up zone
Keep zone
Drooping zone
Stop zone
0˚C
3˚C
5˚C
7˚C
13˚C
A
30
2
When increase
When decrease
(R6034)
Reset zone
Heat exchanger
thermistor
temperature
Up zone
Keep zone
Drooping zone
Stop zone
50˚C
52˚C
54˚C
55˚C
65˚C
Содержание F-Series
Страница 1: ... Applied Models Inverter Multi Cooling Only Inverter Multi Heat Pump F Series SiBE12 713 ...
Страница 11: ...Introduction SiBE12 713 x ...
Страница 47: ...Specifications SiBE12 713 36 Specifications ...
Страница 113: ...Control Specification SiBE12 713 102 Function and Control ...
Страница 122: ...SiBE12 713 Instruction Operation Manual 111 FTK X S 20 25 35 C Names of parts Indoor Unit ...
Страница 235: ...Instruction SiBE12 713 224 Operation Manual ...
Страница 297: ...Check SiBE12 713 286 Service Diagnosis ...
Страница 316: ...SiBE12 713 Outdoor Unit Removal Procedure 305 Step Procedure Points ...
Страница 330: ...SiBE12 713 Others 319 Part 8 Others 1 Others 320 1 1 Test Run from the Remote Controller 320 1 2 Jumper Settings 321 ...