Startup Control
SiUS30-604
62
Function
4. Startup Control
This startup control is used to provide the following control to reduce the compressor load resulting
from liquid return or else during compressor startup, and also determine the position of four way
valves.
4.1
Cooling Start-up Control
Both master and slave units operate same time for changing 4 way valve position
→
Normal
operation after completion.
Parts name
Symbol
Electrical
symbol
Pressure equalization
control before start-up
Starting control
Compressor
—
(M1C)
0 Hz
52Hz
+2 steps/20 sec.
(until Pc-Pe > 71.05 psi)
Inverter cooling fan
—
(M1, 2F)
OFF
Inverter cooling fan
control
4 way valve (Main)
20S1
(Y5S)
Holding
OFF
4 way valve (for heat exchanger)
20S2
(Y7S)
Holding
OFF
Main heat exchanger electronic exp. valve
EV1
(Y1E)
0 pulse
2000 pulse
Sub-cooling electronic exp. valve
EV3
(Y3E)
0 pulse
0 pulse
Hot gas bypass solenoid valve
SVP
(Y1S)
OFF
ON
Water heat exch. oil return solenoid valve
SVE
(Y2S)
OFF
OFF
Receiver gas charging solenoid valve
SVL
(Y3S)
OFF
OFF
Receiver gas discharge solenoid valve
SVG
(Y4S)
OFF
OFF
Non-operation unit liquid pipe stop
solenoid valve
SVSL
(Y6S)
ON
ON
Indoor unit fan
—
(M1, 2F)
Indoor unit control
Indoor unit control
Indoor unit expansion valve
EV
(Y1E)
0 pulse
0 pluse
Initial
opening
BS 20RH
Cooling
20RH
(Y3S)
OFF
OFF
Heating
BS 20RT
20RT
(Y1S)
OFF
OFF
Ending condition
1 minute
Max. 5 minutes
Thermostat ON
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...