SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
157
Troubleshooting
(V2778)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace float switch.
Modify the float switch’s
connection and turn on again.
Connect the drain pump and
turn on again.
Check the drain piping for
clogging or upward slope, etc.
Replace indoor unit PC board.
Replace the drain pump or
check for dirt, etc.
Connect either a short circuit
connector or float switch and
turn on again.
YES
YES
YES
YES
Defect of indoor unit PC board.
Loose connection of connector.
NO
NO
NO
YES
YES
NO
NO
YES
NO
YES
NO
NO
The float
switch is connected to
X8A of the indoor unit
PC board.
NO
The drain
pump works when
the power supply is reset
for the indoor
unit.
The drain
pump is connected
to X25A or terminals Y1
and Y2 of the
indoor unit PC
board.
The voltage
of terminals Y1
and Y2 or X25A is
208~230 V (within
5minutes of resetting
the power
supply).
Water builds up
in the drain pan.
The float
switch contact is
forming a short circuit
(continuity check
with X8A or X15A
disconnected)
A short
circuit connector is
connected to
X8A.
Provide 208~230V power
supply.
YES
NO
Is power supply
208~230V provided?
Becomes
normal when X8A of
the indoor unit PC board
is short circuited
The float switch
functions normally.
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...