SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
181
2.18
“
F3
”
Outside Unit:
Abnormal Discharge Pipe Temperature
Remote
Controller
Display
F3
Applicable
Models
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe temperature
sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level (over 135°C)
When the discharge pipe temperature rises suddenly (over 120°C continues 10 min.)
Supposed
Causes
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdside unit PC board
Troubleshooting
Connect the Service Checker.
Restart operation after resetting
operation.
∗
1: Compare the resistance values of the discharge pipe thermistor with
measurements of a surface thermometer.
(For temperature and resistance characteristics of a thermistor, refer to
page 278, 279.)
∗
2: Compare the discharge pipe temperature checked by the Service
Checker with the resistance of the thermistor (refer to
∗
1).
•
The discharge pipe thermistor is normal and the main PCB
temperature detection is also normal.
•
In fact, discharge pipe temperature is rising.
: Refer to page 251 to eliminate the causes of
overheat operation.
CHECK 3
Is
PCB detection
temperature normal?
(
∗
2)
Replace the main PCB.
NO
YES
Replace the discharge pipe
thermistor.
YES
NO
Are
discharge pipe
thermistor characteristics
normal?
(
∗
1)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...