SiUS30-604
Field Setting
Test Operation
111
Setting by pushbutton switches
The following settings are made by pushbutton switches on PC board.
In case of multi-outside unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED indication as shown below.
(Factory setting)
There are the following three setting modes.
c
Setting mode 1 (H1P off)
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during “abnormal”,
“low noise control” and “demand control”.
d
Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
e
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Mode changing procedure
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
Master unit
7
7
8
7
7
7
7
8
Slave unit 1
7
7
7
7
7
7
7
9
Slave unit 2
7
7
7
7
7
7
7
7
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
(V2760)
Setting mode 1
Monitor mode
H1P
Push the BS1 (MODE button)
one time.
Blinking
MODE
MODE
Off
H1P
Setting mode 2
MODE
On
H1P
Push and hold the BS1
(MODE button) for 5 seconds.
Push the BS1 (MODE button) one time.
(Normal)
(V2761)
Using the MODE button, the modes can be changed as follows.
Check item selection (Set)
Contents display
Monitor mode
Setting mode 1
(Initial condition)
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Setting item selection (Set)
Setting mode 2
(Set): Select mode with BS2 (SET button) in each selection step.
Setting condition
selection (Set)
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS1
(MODE button).
Press BS1
(MODE button).
Press BS1 (MODE button).
Press BS1 (MODE button) for more than 5 sec.
(V2762)
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...