SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
217
Troubleshooting
(V2824)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
Replace the outside unit PC
Board (A1P).
YES
C/H SELECT is set to “IND”.
Cool / heat selection is
unified.
C/H SELECT
is set to “MASTER”.
NO
C/H SELECT
is set to “SLAVE”.
NO
Check
and see if the following items
are normal.
NO
Does a
malfunction occur when
the cool / heat selector is
set to “IND”?
YES
Set C/H SELECT to “IND”.
YES
Fix the outside units multi
connection transmission
wiring and reset power.
NO
Is the
outside units multi
connection transmission
wiring normal?
Is the
indoor / outside unit
transmission wiring
normal?
NO
YES
Fix the indior / outside unit
transmission wiring.
The cool / heat unified
address for outside units in
outside - outside unit
transmission is duplicated.
Set the address correctly.
YES
NO
NO
YES
YES
Replace the outside unit
outside control adaptor.
replacement
Replace the outside unit PC
board (A1P).
External control adaptor for outdoor unit
•
Is there continuity?
•
Does the cool/heat unified address match?
Outside unit (unified master unit)
•
Is there continuity?
•
Does the cool/heat unified address match?
Fix the problem.
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...