Troubleshooting (OP: Unified ON/OFF Controller)
SiUS30-604
252
Troubleshooting
∗
1 : In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (Refer to page 89.)
∗
2 : In heating, the outside unit electronic expansion valve (Y1E) is used for “superheated degree control”. (Refer to page
67.)
∗
3 : Reference values for superheated degree to be used in the judgment of wet operation
Suction gas superheated degree: 37.4
°
F or less
Discharge gas superheated degree: 59
°
F or less,
excluding when it is immediately after startup, under drop control or other specific conditions.
(The values above must be used only for reference purposes. Even it is operated within the range above,
operation may be normal in other conditions.)
Dwelled
refrigerant
Faulty indoor
unit electronic
expansion valve
Faulty outside
unit electronic
expansion valve
Faulty crankcase heater
Faulty
superheated
degree control
Wet operation
[In cooling]
Degradation in
evaporation
capacity
[In heating]
←
Does the water pump function normally?
←
Is the strainer or other parts clogged?
←
Is the water heat exchanger clogged?
←
Is there any obstacle in the
air passage?
←
Is the air filter clogged?
←
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
←
Refer to [CHECK 5]
←
Are the coil resistance and insulation normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
←
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
←
Are the coil resistance and insulation normal?
←
Are the voltage characteristics normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
←
Does the pressure value of the Service Checker
match the reading of the pressure sensor?
←
Is the heat exchanger clogged?
[CHECK 4] Check for causes of wet operation
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Excessive refrigerant
charging
[In cooling]
If the indoor unit
electronic
expansion valve
excessively
opened
(
∗
1)
[In heating]
If the outside unit
electronic
expansion valve
excessively
opened
(
∗
2)
Frequent starts and
stops of the compressor
Faulty control
Faulty control
Dirty evaporator
Decreased
fan airflow
rate
Decreased
fan output
High air
passage
resistance
Faulty valve coil
Faulty valve body
Faulty control PCB
Faulty control PCB
Faulty fan motor
Dirty filter
Obstacle
Clogged water piping system
Faulty water pump
Dirty water heat exchanger
Decrease in
water of the
water heat
exchanger
Faulty control PCB
(including capacity setting)
Faulty valve coil
Faulty valve body
Faulty low pressure sensor
Faulty suction pipe thermistor
Faulty gas pipe thermistor
of indoor unit
Faulty liquid pipe thermistor
of indoor unit
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...