Troubleshooting by Indication on the Remote Controller
Troubleshooting
211
Troubleshooting
YES
YES
NO
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
Replace the inverter PCB
(A2P).
If the inverter PCB is
significantly damaged,
the compressor or the
fan motor may be
damaged as well.
The inverter PCB
(A2P) is damaged.
The "U2" malfunction
recurs.
The compressor
enters standby mode
without completing the
startup sequence.
Connect and disconnect the
following connectors.
X4A (A2P)
↔
X25A (A1P)
X6A (A2P)
↔
X33A (A1P)
Turn ON the power supply, and
then set the RUN switch to ON.
Replace the inverter PCB
(A2P).
If the inverter PCB is
significantly damaged,
check for the
compressor.
Check for every wire
connection.
Continue the compressor
operation.
It is supposed that the
faulty power supply
results from external
causes such as
instantaneous power
failure.
YES
YES
NO
NO
YES
Check for the power supply
conditions.
Does the voltage fall in the
range of 208 to 230V±10%?
Is there any open phase or
erroneous wire connection?
Does the unbalanced voltage
fall within 6V?
Any of the
conditions aforementioned
is defective.
The compressor
has an insulation resistance
of 100k
Ω
or less.
Remedy the defective
conditions.
Replace the compressor.
Replace the inverter PCB
(A2P).
Is the
power transistor normal?
∗
∗
Power transistor check: Refer page 281.
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...