Precautions for New Refrigerant (R-410A)
SiUS30-604
284
Precautions for New Refrigerant (R-410A)
1.
Precautions for New Refrigerant (R-410A)
1.1
Outline
1.1.1
About Refrigerant R-410A
Characteristics of new refrigerant, R-410A
1. Performance
Almost the same performance as R-22 and R-407C
2. Pressure
Working pressure is approx. 1.4 times more than R-22 and R-407C.
3. Refrigerant composition
Few problems in composition control, since it is a Quasi-azeotropic mixture refrigerant.
★
1. Non-azeotropic mixture refrigerant: mixture of two or more refrigerants having different boiling
points.
★
2. Quasi-azeotropic mixture refrigerant: mixture of two or more refrigerants having similar boiling
points.
★
3. The design pressure is different at each product. Please refer to the installation manual for
each product.
(Reference) 1 MPa
10.19716 kgf / cm
2
1 MPa
145 psi
HFC units (Units using new refrigerants)
HCFC units
Refrigerant name
R-407C
R-410A
R-22
Composing
substances
Non-azeotropic mixture
of HFC32, HFC125 and
HFC134a (*1)
Quasi-azeotropic mixture
of HFC32 and JFC125
(*1)
Single-component
refrigerant
Design pressure
3.2 MPa (gauge pressure)
= 32.6 kgf/cm
2
= 464 psi
4.0 MPa
(gauge
pressure)
= 40.8 kgf/cm
2
= 580 psi
2.75MPa
(gauge pressure)
= 28.0 kgf/cm
2
= 399 psi
Refrigerant oil
Synthetic oil (Ether)
Mineral oil (Suniso)
Ozone destruction
factor (ODP)
0
0
0.05
Combustibility
None
None
None
Toxicity
None
None
None
Pressure-Enthalpy curves of HFC-32/125 (50/50wt%)
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...