SiUS30-604
Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting
249
←
Refer to [CHECK 5] on page 253.
←
Is the indoor unit too small for the large-sized outside unit?
[CHECK 1] Check for causes of rise in high pressure
Referring to the Fault Tree Analysis (FTA) shown below, identify the faulty points.
Rise in high
pressure
Local
pressure
rise
Faulty high
pressure
control
Faulty outside
unit electronic
expansion valve
Faulty
control
Faulty indoor
unit electronic
expansion valve
Stop valve closed
Faulty high pressure sensor
[In cooling]
If the outside unit
electronic
expansion valve
is throttled
(
∗
1)
Dirty water heat exchanger
Decrease in water
of the water heat
exchanger
Mixing-in of non-condensable gas
Degradation in
condensing
capacity
Clogged water piping system
[In cooling]
[In heating]
←
Check to be sure the stop valve is open.
←
Conduct visual checks for pipe conditions.
←
Is there any temperature difference around
the filter or the branch pipe?
←
Are the coil resistance and insulation normal?
←
Are the voltage characteristics normal?
←
Does the pressure value of the Service
Checker match the reading of the
pressure sensor?
←
Are the coil resistance and insulation normal?
←
Are the voltage characteristics normal?
←
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
←
Does the pressure value of the Service
Checker match the reading of the pressure
sensor?
←
Is the heat exchanger clogged (in cooling)?
←
Is air or else mixed in the refrigerant system?
←
Is the water temperature at the inlet not
more than 113
°
F?
←
Does the water pump function normally?
←
Is the strainer or the like clogged?
←
Is the suction air temperature not more
than 80.6
°
F?
←
Is air or else mixed in
the refrigerant system?
←
Is the indoor temperature not more
than 80.6
°
F?
←
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
←
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
←
If a spare PCB is mounted, is the
capacity setting properly made?
←
Is the air filter clogged?
←
Is there any obstacle in the air
passage?
Excessive refrigerant charging
Improper mode selection
[In heating]
∗
1 : In cooling, the outside unit electronic expansion valve (Y1E) is fully open in normal condition.
∗
2 : In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(Refer to “Electronic Expansion Valve Control” on page 89)
[In heating]
If the indoor unit
electronic
expansion valve
excessively throttled
(
∗
2)
High pipe
resistance
A temperature difference in
excess of 10
°
C between the inlet and
the outlet is deemed to be abnormal.
Faulty
control
Bent and Crush of
pipe
Clogging of foreign
particles
Faulty valve coil
Faulty valve body
Faulty high pressure sensor
Faulty control PCB
Faulty indoor unit
liquid pipe thermistor
Faulty valve coil
Faulty valve body
Faulty control PCB
High water temperature at the water heat exchanger inlet
Faulty water pump
Short circuit
High ambient temperature
Faulty fan motor
Dirty filter
Obstacle
Faulty control PCB
(including capacity
setting)
Mixing-in of non-condensable gas
High suction air
temperature of
indoor unit
Decreased
fan airflow
rate
Decreased
fan output
High air
passage
resistance
Faulty suction air thermistor of indoor unit
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...