SiUS30-604
Field Setting
Test Operation
135
3.2.9 Power Transistor Check Operation
When the inverter system malfunctions (malfunction of inverter, INV compressor), to locate where
the malfunction occurs, switching to the power transistor check mode of inverter in the service
mode setting enables not to judge the position detection signal malfunction but to output waveform
only during inverter operation. (The waveform can be checked by disconnecting the wiring of
compressor.)
After the completion of checks, return the system to the previous mode and wait for 30 seconds or
more until the discharge of capacitor is completed. Then, conduct a subsequent work.
Notes:
Be sure to disconnect the compressor wiring when conducting the check operation mentioned
above.
When the output voltage is approx. 100~200 V (10 Hz) and the voltage balance between phases
U-V, V-W, W-U is within ±5%, the inverter PCB is normal.
Refer the detail power transistor check to page 281.
3.2.10 Emergency Operation
If the compressor cannot operate, this control inhibits any applicable compressor or outside unit
from operating to perform emergency operation only with the operative compressor or outside unit.
3.2.11 Restrictions for Emergency Operation
• If the emergency operation is set while the outside unit is in operation, the outside unit stops once
after pump-down residual operation (a maximum of 5 minutes elapsed).
3.2.12 In the Case of Multi-Outside-Unit System
Automatic backup operation
With multi-outside-unit system, if a certain outside unit system malfunctions (i.e., the system
stops and indoor unit remote controller displays the malfunction), by resetting the system with the
indoor unit remote controller, the applicable outdoor unit is inhibited from operating for 8 hours,
thus making it possible to perform emergency operation automatically.
However, in the event any of the following malfunctions occurs, automatic backup operation can
be performed.
Malfunctions under which automatic backup operation can be performed:
• E3, E4, E5, E7
• F3
• H7, H9
• J2, J3, J5, J6, J7, J9, JA, JC
• L3, L4, L5, L8, L9, LC
• U2, UJ
Caution
For making a compressor unable to operate due to malfunction, etc., be sure to conduct
the work with emergency operation setting.
Never execute work such as disconnection of the power cable from magnet contactor.
(Otherwise, other normal compressors may malfunction.)
∗
Because the units will be operated in the combination with which oil pressure
equalization between compressors cannot be performed.
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...