Troubleshooting by Indication on the Remote Controller
SiUS30-604
226
Troubleshooting
2.49
“
UF
”
Refrigerant System not Set, Incompatible Wiring/
Piping
Remote
Controller
Display
UF
Applicable
Models
All models of indoor units
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
On check operation, the number of indoor units in terms of transmission is not corresponding to that
of indoor units that have made changes in temperature.
Malfunction
Decision
Conditions
The malfunction is determined as soon as the abnormality aforementioned is detected through
checking the system for any erroneous connection of units on the check operation.
Supposed
Causes
Improper connection of transmission wiring between outside unit and external control adaptor
for outdoor unit.
Failure to execute wiring check operation
Defect of indoor unit PC board
Troubleshooting
Note:
Test operation may not be successful if carried out after the outside unit has been off for more than
12 hours, or if it is not carried out after running all connected indoor units in the fan mode for at least
an hour.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2830)
Is
indoor - outside
and outside - outside unit
transmission wiring
normal?
Replace indoor unit PC board.
Test operation may not have
been carried out successfully.
After fixing incorrect wiring,
push and hold the RESET
button on the master outside
unit PC board for 5 seconds.
YES
NO
YES
NO
NO
YES
Is the
test operation
(Wiring check operation)
carried out?
Is indoor
-outside and outside-
outside unit transmission
wiring normal?
Open stop valve.
YES
NO
Are the stop
valves openned?
∗
The unit will not run for up to
12 minutes.
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...