SiUS30-604
Field Setting
Test Operation
99
3.
Field Setting
3.1
Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be required
to change. Refer to information in the option handbook.)
3.1.1 Wired Remote Controller <BRC1C71>
1. When in the normal mode, push the
button for 4 seconds or more, and operation then
enters the “field set mode”.
2. Select the desired “mode No.” with the
button.
3. During group control and you want to set by each individual indoor unit (when mode No. 20, 21,
22, 23, 25 has been selected), push the time mode
button and select the “indoor unit
No.” to be set.
Note: This operation is not required when setting as a group.
4. Push the
button and select the first code No.
5. Push the
button and select the second code No.
6. Push the timer
button one time and “define” the currently set contents.
7. Push the
button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode No.
to “10”, Mode setting No. to “0” and setting position No. to “02”.
Содержание BSVQ36MVJU
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Страница 13: ...Introduction SiUS30 604 xii ...
Страница 27: ...Capacity Range SiUS30 604 14 General Information ...
Страница 49: ...Specifications SiUS30 604 36 Specifications ...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92 ...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box ...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419 ...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A ...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116 ...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420 ...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Страница 309: ...SiUS39 601 iv Index ...