SiBE121135
Indoor Unit Control (RA Models)
Function and Control
77
Drawing of
Inverter
The following drawing shows a schematic view of the inverter principle:
Inverter Features
The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor
temperature and cooling / heating load.
Quick heating and quick cooling
The compressor rotational speed is increased when starting the heating (or cooling). This
enables to reach the set temperature quickly.
Even during extreme cold weather, high capacity is achieved. It is maintained even when the
outdoor temperature is 2°C.
Comfortable air conditioning
A fine adjustment is integrated to keep the room temperature constant.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency Limits
The following functions regulate the minimum and maximum frequency:
Forced Operation
Refer to page 405 for detail.
Refrigerant circulation rate (high)
high f
low f
freq=variable
Refrigerant circulation rate (low)
high speed
low speed
(R2812)
Amount of heat
exchanged air (large)
Amount of heat
exchanged air (small)
freq=
constant
capacity=
variable
AC
po
w
er
DC
po
w
er
Amount of heat
exchanged air (large)
Amount of heat
exchanged air (small)
50 Hz
60 Hz
Frequency
Functions
Low
Four way valve operation compensation. Refer to page 111.
High
Compressor protection function. Refer to page 112.
Discharge pipe temperature control. Refer to page 112.
Input current control. Refer to page 113.
Freeze-up protection control. Refer to page 113.
Heating peak-cut control. Refer to page 114.
Defrost control. Refer to page 116.
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...