Trial Operation
SiBE121135
408
Trial Operation and Field Settings
4. Trial Operation
4.1
RA Indoor Unit - FTXG, FTXS, CTXS, FVXG, FVXS, FLXS,
FDXS Series
Outline
1. Measure the power supply voltage and make sure that it falls in the specified range.
2. Trial operation should be carried out in either cooling or heating operation.
3. Carry out the trial operation in accordance with the operation manual to ensure that all
functions and parts, such as flap movement, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is
not to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system backs up the
operation mode. The system then restarts operation with the previous operation mode when
the circuit breaker is restored.
In cooling operation, select the lowest programmable temperature; in heating operation, select
the highest programmable temperature.
Trial operation may be disabled in either operation mode depending on the room
temperature.
After trial operation is complete, set the temperature to a normal level.
(26°C ~ 28°C in cooling, 20°C ~ 24°C in heating)
For protection, the system does not start for 3 minutes after it is turned off.
Detail
ARC466 Series
(1) Press the [On/Off] button to turn on the system.
(2) Press the center of the [Temp] button and the [Mode] button at the same time.
(3) Select
T
(trial operation) with the [Temp]
or button.
(4) Press the [Mode] button to start the trial operation.
(5) Press the [Mode] button and select operation mode.
(6) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a
trial operation, press the [On/Off] button.
(R11676)
(2) (4) (5)
(1) (6)
(2) (3)
(3)
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...