Wiring Error Check Function
SiBE121135
406
Trial Operation and Field Settings
3. Wiring Error Check Function
Outline
The convenient wiring error check function is designed for the microcomputer to correct wiring
errors itself.
If local wiring is unclear in the case of buried piping, for example, just press the wiring error
check switch that is behind the stop valve cover of the outdoor unit. Even if the connections for
Room A and Room B are confused, the system may run without a hassle. Note that this check
function does not work in the following cases.
For about 1 minute after the power is turned on (during initial setup).
For 3-minute standby period after the compressor has stopped.
When the outdoor temperature is below 5°C.
If the indoor unit is in trouble (also in case of all-room transmission failure).
When the piping and wiring are perfect, there is no need to use this function.
Operation
1. Remove the stop valve cover.
2. Press the wiring error check switch (SW3) on the service monitor PCB of the outdoor unit,
and the wiring error check function is activated.
3. In about 10 ~ 20 minutes, the check finishes automatically.
4. When the check is over, the service monitor LED indicators start blinking.
Self-correction complete…The LED indicators 1 ~ 3 (3-room model), 1 ~ 4 (4-room model),
or 1~5 (5-room model) blink one after another.
Self-correction impossible…The LED indicators blink all at the same time.
∗
Transmission failure occurs at any of the indoor units.
∗
The indoor unit heat exchanger thermistor is disconnected.
∗
An indoor unit is in trouble (if a trouble occurs during the wiring error checking).
Emergency stop…Any of the LED indicators stays on.
Note:
1. It takes about 10 ~ 20 minutes (after pressing the wiring error check switch) to complete the
checking.
2. Wrongly connected liquid and gas pipes cannot be self-corrected. Be sure to make the liquid
pipe and the gas pipe in pairs.
3. To cancel the wiring error check procedure halfway, press the wiring error check switch
again.
In this case, the memory of the microcomputer returns to its initial status (Room A wiring
→
Port A piping, Room B wiring
→
Port B piping).
4. When replacing the outdoor unit PCB, be sure to use this function.
5. Make the power side setting after doing the wiring error check. (Otherwise, if the wiring is
reversed, the air-conditioners being connected are set up in the reverse way.)
LED
1
2
3
4
5
Judgment
Status
All blinking at once
Self-correction impossible
Blinking one after another
Self-correction complete
Service monitor PCB
Wiring error
check switch
(SW3)
(R12871)
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...