SiBE121135
Wiring Error Check Function
Trial Operation and Field Settings
407
Basic Knowledge
Refrigerant flows from Port A and on. The temperatures of the indoor heat exchanger
thermistors are detected one by one to check up the matching between the piping and
wiring.
With this function on, freezing (crackling) noise may be heard from the indoor unit. This is
not a problem. (This is because the heat exchanger temperature is made to drop below 0°C
in order to increase the detection accuracy.)
The indoor fan is made to turn on or off at the same time.
Checking the
current setting
data on the
microcomputer
memory
Those data can be checked by looking at the service monitor LED indicators, when the wiring
error checking is over, during forced operation, at the stop of the system.
The LED indicators stop blinking when the forced operation is over.
LED1…Room A wiring, LED2…Room B wiring
1st blinking LED…Port A piping, 2nd blinking LED…Port B piping
The 1st blinking LED means the room that is connected with Port A. The 2nd blinking LED
means the one connected with Port B.
Example
Ex: Suppose the LED indicators are blinking as follows.
The above means that Port A is connected with Port B, and Port B with Room A (or self-
corrected this way.)
A 1 2 3 4
Green Red
Green Red
Green Red
A 1 2 3 4
A 1 2 3 4
(R8252)
L
E
D
L
E
D
L
E
D
A
B
Wiring
Piping
A
B
(R8253)
Wiring
Piping
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...