Troubleshooting for Outdoor Unit
SiBE121135
322
Service Diagnosis
Troubleshooting
Check No.17
Refer to P.333
Check No.19
Refer to P.334
Note:
Refer to “Application of silicon grease to a power transistor and a diode bridge” on page 423 for
detail.
(R16053)
Caution
NO
Slightly dirty
NG
Too dirty
OK
NO
YES
Turn off the power and turn it on
again
to start the system.
Check the radiation fin
temperature.
Check No. 17
Check the installation condition.
NO
YES
YES
Above
A
˚C?
Radiation fin dirty?
Check No. 19
Check the outdoor fan or
related.
Error displayed again?
Has the PCB been
replaced?
Check if applied properly on
the radiation fin. If not,
apply the silicon grease (
∗
).
(See Note.)
∗
Silicon grease
Part No.: 1
172698
Replace the outdoor unit
PCB.
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB.
A
(°C)
40/50/52/58/68/75 class
103
80/90 class
105
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...