Control Specification
SiBE121135
122
Function and Control
4.13 Malfunctions
4.13.1 Sensor Malfunction Detection
Sensor malfunction may occur either in the thermistor or current transformer (CT) system.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Gas pipe thermistor
5. Outdoor temperature thermistor
6. Liquid pipe thermistor
Relating to CT Malfunction
Refer to “CT or related abnormality” on page 315 for detail.
4.13.2 Detection of Overcurrent and Overload
Outline
In order to protect the inverter, an excessive output current is detected and the OL temperature
is observed to protect the compressor.
Detail
If the inverter current exceeds 14 ~ 20 A (depending on the model), the system shuts down
the compressor.
If the OL (compressor head) temperature exceeds 120 ~ 130°C, the compressor stops.
4.13.3 Refrigerant Shortage Control
Outline
I : Detecting by power consumption
If the power consumption is below the specified value and the frequency is higher than the
specified frequency, it is regarded as refrigerant shortage.
The power consumption is low comparing with that in the normal operation when refrigerant is
insufficient, and refrigerant shortage is detected by checking power consumption.
II : Detecting by discharge pipe temperature
If the discharge pipe temperature is higher than the target discharge pipe temperature, and the
outdoor electronic expansion valve is fully open for more than the specified time, it is regarded
as refrigerant shortage.
Refer to “Refrigerant shortage” on page 296 for detail.
Frequency
Power consumption
Refrigerant shortage zone
(R11685)
40 ~ 55 Hz
(depending on
the model)
(R1391)
Refrigerant shortage
zone
Target discharge
pipe temperature
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...