Indoor Unit Control (SA Models)
Function and Control
99
2. Indoor Unit Control (SA Models)
2.1
Drain Pump Control
2.1.1 When the Float Switch is Tripped While the Cooling Thermostat is
ON:
∗
1. (Normal operation):
The purpose of residual operation is to completely drain any moisture adhering to the fin of the
indoor heat exchanger when the thermostat goes off during cooling operation.
∗
2. (Malfunction residual):
The remote controller displays
A3
and the air conditioner comes to an abnormal stop in 5
minutes if the float switch is turned OFF while the cooling thermostat is ON.
2.1.2 When the Float Switch is Tripped While the Cooling Thermostat is
OFF:
∗
3. (Malfunction residual):
The remote controller displays
A3
and the air conditioner comes to an abnormal stop if the float
switch is turned OFF and not turned ON again within 5 minutes while the cooling thermostat is
OFF.
Float switch
The remote controller displays
A3
and the indoor unit stops.
∗
2) Malfunction residual
∗
1) Normal operation
5 min. 5 sec.
5 min.
Drain pump
Thermostat
(running)
(R16092)
ON
ON
OFF
OFF
ON
OFF
Float switch
Drain pump
Thermostat
(running)
ON
ON
OFF
OFF
ON
OFF
The indoor unit enters malfunction treatment if the float switch is not
reset within 5 minutes.
The remote controller displays
A3
and the indoor unit stops.
∗
3
5 sec.
5 sec.
5 min.
5 min.
(R16093)
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...