SiBE121135
Troubleshooting with LED
Service Diagnosis
251
Caution:
When operation stops suddenly and the operation lamp blinks, it could be "operation mode
conflict".
Check followings;
Are the operation modes all the same for the indoor units connected to multi system outdoor
unit?
If not, set all the indoor units to the same operation mode and confirm that the operation lamp is
not blinking.
Moreover, when the operation mode is automatic, set all the indoor unit operation mode as
"cooling" or "heating" and check again if the operation lamp is normal.
If the lamp stops blinking after the above steps, there is no malfunction.
∗
Operation stops and operation lamp blinks only for indoor unit which different operation mode
is set later. (The first set operation mode has priority.)
Service Monitor
The indoor unit has one green LED (LED A) on the control PCB. When the microcomputer
works in order, the LED A blinks.
Floor Standing Type: FVXS Series
Floor / Ceiling Suspended Dual Type
Duct Connected Type
BRC1D528
BRC1E52A7, BRC1E52B7
(R11687)
Operation lamp (green)
Operation lamp (green)
(R11688)
Operation lamp (green)
(Q0340)
Operation lamp (red)
(R12851)
Operation lamp (green)
(R17162)
+
The error or warning message also
blinks on the basic screen.
+
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...