SiBE121135
Function of Thermistor
Function and Control
105
3. Function of Thermistor
Illustrations are for 4-room models as representative and have 4 lines of indoor unit system
(A ~ D). 3-room models have 3 lines (A ~ C) and 5-room models have 5 lines (A ~ E).
Cooling Only Model
Heat Pump Model
(1) Outdoor Heat
Exchanger
Thermistor
1. The outdoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the
outdoor and indoor heat exchanger temperature, and controls the outdoor electronic
expansion valve opening so that the target discharge pipe temperature can be obtained.
2. In cooling operation, the outdoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature
becomes lower than the outdoor heat exchanger temperature, the discharge pipe thermistor
is judged as disconnected.
3. In cooling operation, the outdoor heat exchanger thermistor is used for high pressure
protection.
EVC
EVD
EVB
EVA
Compressor
(1)
(2)
(3)
(4)
(R17248)
D
C
B
A
Outdoor electronic
expansion valve
Four way valve
Compressor
EVC
EVD
EVB
EVA
(1)
(2)
(3)
(4)
(5)
(R17159)
D
C
B
Radiant panel
A: In case of FVXG model
Indoor electronic
expansion valve
(Motor operated
valve)
(4)
(6)
φ
6
(6)
φ
4
Outdoor electronic
expansion valve
Содержание 3MXS40K2V1B
Страница 187: ...SiBE121135 RA Indoor Unit Operation Manual 175 2 1 17 Quick Reference FTXG25 35 50JV1BW A Quick Reference ...
Страница 188: ...RA Indoor Unit SiBE121135 176 Operation Manual FTXS20 25K2V1B CTXS15 35K2V1B Quick Reference ...
Страница 189: ...SiBE121135 RA Indoor Unit Operation Manual 177 FVXG25 35 50K2V1B Quick Reference ...
Страница 246: ...SA Indoor Unit SiBE121135 234 Operation Manual 2 Start 5s 5s 5s 5s 5s End ...
Страница 413: ...SiBE121135 Outdoor Unit 80 90 Class Removal Procedure 401 7 Remove the sound blanket inner Step Procedure Points R10439 ...