SiBE121135
Outdoor Unit: 80/90 Class
Removal Procedure
383
4
Disconnect the
connector for the four
way valve coil [S80].
Pull out the clamp.
The cooling only model has
no harness for [S80].
5
Disconnect the
connectors for the
electronic expansion
valve coil.
[S20] (white): room A
[S21] (red): room B
[S22] (blue): room C
[S23] (yellow): room D
Pull out the clamp.
5-room models also has
[S24] (green) for room E.
When reassembling, insert
each clamp into the small
hole.
6
Disconnect the
connector for the liquid
pipe thermistor [S93].
Pull out the clamp.
Step
Procedure
Points
[S80]
Clamp
(R11187)
A
B
C
D
Clamp
(R11188)
For the electronic
expansion valve coil
[S93]
(R17266)
Clamp
[S93]
(R10400)