Query
Field Name
Example (hex)
ASCII code
RTU 8-Bit Field
Header
‘ : ’ (Colon)
None
Slave Address
F0
F 0
1111 0110
Function
03
0 3
0000 0011
Start Address Hi
00
0 0
0000 0000
Start Address Lo
80
8 0
1000 0000
No. of Register Hi
00
0 0
0000 0000
No. of Register Lo
03
0 3
0000 0011
Error Check
LRC (2 chars)
CRC (16 bits)
Trailer
CR LF
None
Total Bytes
17
8
Response
Field Name
Example (hex)
ASCII code
RTU 8-Bit Field
Header
‘ : ’ (colon)
None
Slave Address
F0
F 0
1111 0000
Function
03
0 3
0000 0011
Byte Count
06
0 6
0000 0110
1
st
Data Hi
03
0 3
0000 0011
1
st
Data Lo
E8
E 8
1110 1000
2
nd
Data Hi
00
0 0
0000 0000
2
nd
Data Lo
07
0 7
0000 0111
3
rd
Data Hi
00
0 0
0000 0000
3
rd
Data Lo
00
0 0
0000 0000
Error Check
LRC (2 chars)
CRC (16 bits)
Trailer
CR LF
None
Total Bytes
23
11