B. Data structure in communication
This product support MODBUS RTU and MODBUS ASCII protocol.
In ASCII mode, every byte of the data will transfer to two ASCII code.
Ex. If byte data is 63H, it will be 36H, 33H in ASCII code.
(1) Hex to ASCII code transfer table
Char
‘ 0 ’
‘ 1 ’
‘ 2 ’
‘ 3 ’
‘ 4 ’
‘ 5 ’
‘ 6 ’
‘ 7 ’
ASCII code
30H
31H
32H
33H
34H
35H
36H
37H
Char
‘ 8 ’
‘ 9 ’
‘ A ’
‘ B ’
‘ C ’
‘ D ’
‘ E ’
‘ F ’
ASCII code
38H
39H
41H
42H
43H
44H
45H
46H
Char
‘ : ‘
CR
LF
ASCII code
3AH
0DH
0AH
(2) The data frame format explain
Field Name
Explain
Header
Data frame initial character
Slave Address
Inverter communication address
Function
Function code
Start Address
Enquiry feedback data initial address
No. of Register
Enquiry feedback data (word)
Byte Count
Feedback data(byte)
Data
Feedback data
Register Address
Enquiry modified data address
Preset Data
Modified data
Error Check
Checksum
Trailer
Data frame stop character
C. Function code in Modbus
This product supports Function code 03H and 06H in MODBUS protocol.
(1) Function 03H
:
Read holding register
Read the binary contents of holding registers (4 x references) in the slave. Broadcast is
not supported. The maximum parameters supported by various controller models are
listed on page.
Ex: Read data from 3 continuous addresses in register. The beginning address is 0080H,
the data frame are listed as follow.