32
Output
Frequency
t
Set frequency
Start frequency
Cd16
DC braking time in starting
Cd23,Cd26
DC braking frequency
in stopping
Cd24
DC braking time in stopping
Cd23,Cd26
Instant
initial
field time
Cd65
Output
voltage
DC braking voltage
Cd25
Output voltage of
start frequency
t
Output voltage of
set frequency
§
Cd66
Digital filter function (Settable range 1-6)
This function is adjustable during revolution
This is function is active as digital filter while invert with external analogue input.
Increasing the figure to stabilized frequency while noise of external analogue input is
higher. Decrease the figure when inverter required to response faster.
Cd 66
Digital filter time
1
4 ms
2
8 ms
3
16 ms
4
32 ms
5
64 ms
6
128 ms
§
Cd67
Power source positioning accuracy calibration (Settable range 0-20)
This function is adjustable during revolution
This function is to adjust the calibration of voltage positioning on DC BUS between
detected and actual position. The display value of Cd02=3 will be lower when Cd67
set at bigger figure. Cd02=3 display will be higher when Cd67 setting at smaller figure.