20
§
Cd22
Jump frequency width (Settable range 0-6)
This function must accommodate Cd20 and Cd21
§
Cd23
Braking mode (Settable range 0-3)
This function must accommodate Cd24, Cd25, and Cd26.
Cd23=0 No DC braking
Cd23=1 Stop mode
Cd23=2 Start mode
Cd23=3 Stop and start mode
§
Cd24
DC braking frequency (Settable range 1~60)
This function must accommodate Cd23, Cd25, and Cd26.
Set frequency of DC brake starts at the time of inverter deceleration stops,
the DC brake is active when operates below the starting frequency.
§
Cd25
DC braking voltage (Settable range 1~15)
This function must accommodate Cd23, CD24, and Cd26.
DC braking torque setting
Cd25=1-15, the higher value the higher output brake torque
Note: When DC brake voltage is high, be aware of over current.
§
Cd26
DC braking time (Settable range 1~60)
Adjust DC braking time
Braking Time
Braking
Frequency
Time
Time
Braking
Rate
Start
Frequency
O
u
tp
u
t
F
re
q
u
e
n
c
y
B
ra
k
in
g
V
o
lt
a
g
e
Note:
1. DC braking time too long or too many times is possible to cause motor damage
because of overheating.
2. Set Cd23=0 when DC braking is not required.
Содержание CT-2000ES