
34
Cd80=0 RS485 shut down communication interface.
Cd80=1 Active RTU Mode(8,n,1). Parameter change is not allowed.
Cd80=2 Active RTU Mode(8,n,1). Allow changes on general parameter.
Cd80=3 Active RTU Mode(8,n,1). Allow changes on operation instruction and general
parameter.
§
Cd81
RS485 communication address setting (settable range 1-240)
This function cannot be modified during revolution
Corresponding communication address should be set in advance when active RS485
communication function. Inverter is at slave side.
Note: Communication function refers to manuals of interface.
§
Cd82
Series communication baud rate setting (settable range 0-3
)
This function can’t be modified during revolution.
Setting of Baud rate during communication
Cd82=0 2400 bps
Cd82=1 4800 bps
Cd82=2 9600 bps
Cd82=3 19200 bps
Note: Re-start inverter after setting Baud rate.
§
Cd83
Series communication response time setting
(
settable range 0-15
)
This function can’t be modified during revolution.
Setting waiting time for response when inverter receive correction data.
MODBUS RESPONE TIME=4ms * CD83
§
Cd90
Series communication parameter store eeprom
(
settable range 0
~
1
)
Cd90=0 unstore
Cd90=1 store one data and reset 0
§
CE00,01,02,03
Failure record
Record cause of failure, in order to solve failure.
Note: 1. Cannot record failure Err, Ero, Erc.
2. Only memorize 4 records.
3. Cannot record inverter stopped by low voltage.
4. Read only Cd00,01,02,03 or delete all (Code 36), cannot put in failure record
by operator.
Содержание CT-2000ES
Страница 7: ...7 G Control circuit...