Cd17
Upper limiter of frequency (Selective range 10~240)
This limiter is used to operate within upper limit frequency of motor
Avoid input errors caused by the panel keys and result in mechanical damage.
§
Cd18
Lower limiter of frequency (Settable range 0.5~100)
This limiter is used to operate within lower limit frequency of motor
FH
Output
Frequency
Upper
Limiter
Lower
Limiter
Set Frequency Operation
§
Cd19
Acceleration / deceleration time of jogging (Settable range
0.10~30.00)
Time needed for set frequency from 0Hz to 50Hz.
Set Value (T) = (50 - 0) /
△
F
×
T1
T1: Time needed for acceleration/deceleration
△
F: Frequency changed
§
Cd20, 21
Jump frequency (Settable range 0~240)
This function is to avoid mechanical resonance frequency
Frequency operation automatically jumps to point
+
/
-
jump width (set by Cd22)
This function is only available on constant speed operation, not influence
during acceleration/deceleration, it is settable at 2 points.
Cd21
Cd22
Cd20
Cd22
Time
Output
Frequency